PVC insulated, non-sheathed cable for internal wiring, single core and twisted twin cable, up to 450/750V.
Application:
In dry rooms, apparatus, switch and distribution boards, for fixed installation in conduits, over and under plaster and on insulated supports over plaster. Direct laying in plaster is not permitted.
Minimum bending radius: 4 times of maximum overall diameter.
Standard:
ISIRI (607)01
ISIRI (607)05
IEC (60227)01
IEC (60227)05
BS 6004
HD 21
Construction:
Annealed copper conductor, class 1&2.
PVC insulation, type C.
General Specification:
Working temperature: Max. 70°C.
Harmonized code designation and rated voltage:
solid conductor: H 05V-U (300/500V), H07V-U (450/750V), stranded conductor: H05V-R (300/500V), H07V-R (450/750V)
PVC insulated, non-sheathed, heat resisting cable for internal wiring, single core and twisted twin, up to 300/500V.
Application:
In dry rooms, apparatus, switch and distribution boards, for fixed installation in conduits, over and under plaster and on insulated supports over plaster. Direct laying in plaster is not permitted.
Minimum bending radius: 4 times of maximum overall diameter.
Standard:
ISIRI (607)07
ISIRI (607)08
IEC (60227)07
IEC (60227)08
BS 6004
HD 21
Construction:
Annealed copper conductor, class 1, 2 &5.
PVC insulation, type E.
General Specification:
Rated Voltage: 300/500V.
Working temperature: Max. 90°C.
Harmonized code designation:
solid conductor: H05V2-U, stranded conductor: H05V2-R & flexible conductor: H05V2-K
PVC insulated, PVC sheathed light cable, circular twin, 3-core, 4-core and 5-core, 300/500V.
Application:
In dry, damp and wet locations, on premises and outdoors. For permanent installation above, on, in and under plaster. Not suitable for imbedding in concrete.
Standard:
ISIRI (607)10
IEC (60227)10
BS 6004
HD 21
Construction:
Annealed solid or stranded copper conductor, class 1 &2.
PVC insulation, type C.
Cores twisted together.
Inner covering filling compound.
PVC sheath type ST4.
General Specification:
Rated Voltage: 300/500V.
Working temperature: Max. 70°C.
PVC insulated, non-sheathed cable, 450/750 V, single core for installation at low temperatures, 450/750V.
Application:
In dry rooms, apparatus, switch and distribution boards, for fixed installation in conduits, over and under plaster and on insulated supports over plaster. Direct laying in plaster is not permitted.
Minimum bending radius: 4 times of maximum overall diameter.
Standard:
BS 6004
HD 21
Construction:
Annealed copper conductor, class 1, 2&5.
PVC insulation, type TI 4.
General Specification:
Rated Voltage: 450/750V.
Working temperature: Max. 70°C.
Harmonized code designation:
Solid conductor: H07V3-U, stranded conductor: H07V3-R, flexible conductor: H07V3-K.
PVC insulated, PVC sheathed, single core, flat twin, and 3-core, 300/500V.
Application:
Used in internal wiring for power and lighting.
Standard:
BS 6004
Construction:
Plain annealed copper conductor, class 1 & 2.
PVC insulation, type TI 1.
PVC sheath type 6.
General Specification:
Rated Voltage: 300/500V.
Working temperature: Max. 70°C.
PVC insulated, PVC sheathed cable, with circuit protective conductor, single core, flat twin and 3-core, 300/500V.
Application:
Used in internal wiring for power and lighting.
Standard:
BS 6004
Construction:
Plain annealed copper conductor, class 1 & 2.
PVC insulation, type TI 1.
Parallel circuit protective bare conductor.
PVC sheath type 6.
General Specification:
Rated Voltage: 300/500V.
Working temperature: Max. 70°C.